Calculation for Generator sizing Procedure The generator sizing is done based on the following conditions. a) Load Calculate from continuous. b) 10 % spare capacity for future loads. A) Calculation of total load: Total connected load as per load summary given below. (Refer to generator sizing-load-summary details ) Continuous Load Total KW 237.22 Total KVAR 0.00 Total KVA 279.08 Minimum KW =237.22 KW Maximum KVA =279.08 B) Calculation for Generator Capacity Generator Capacity (In KVA) =Maximum Load X 1.1 = 306.99 KVA (Considering 10% spare capacity for future loads) So we select…